There is a generally recognised method of approaching fault-finding , which is referred to as the 5-Point FaultFinding
It is understood that sometimes it is not easy to get this information, as you may be the only person on site & no one is there to explain ‘what happened’, but you need to go the extra half mile to find out, as it will make your job much easier... Standard/Fundamental Faults Loss of Supply Earth Fault Dead Short Correct Protective Device in place Defective Components Breakdown of Control Circuits Reversed Polarity Mostly seen in Industry Initial Faults on newly Installed work
Some details of the symptoms, cause & effects of various faults are...
Polarity:
Definition: Ensuring that all fuses, switches and circuit breakers are in the phase conductor only, & that all socket outlet & power accessories are wired correctly (Ph to Ph terminal, Neutral to Neutral terminal, etc) The Polarity referred to throughout this section is not the type of Polarity referred to in electronics, where if the positive and the negative points of a circuit are reversed damage could be caused to a component or a circuit board. Incorrect Polarity in fixed Electrical Installations could give risk to electric shock where a circuit is thought to be switched off, when in fact a live terminal remains within the fixture. In figure 2 (other side of this sheet), the problem with LIVE POLARITY is highlighted. The terminals in the under-section of a kWh meter are normally as follows: (from left to right) PH – N – N – PH
PH – N (230V expected) Finally, look closely at Figure 3. The first rose is wired correctly & how would be expected, although the second is a complete wiring confusion, with the lamp wired across the Neutral and the loop and no wiring in the switch-plate. In this case if the wiring were terminated across a one way switch, it would not in fact turn the lamp on and off – the lamp would be perpetually receiving a phase and a neutral, & therefore stay ‘on’. The far greater problem than a lamp that will not switch off is that there would be 230V present across the switch (ie: if you placed a lamp holder from Common to L1 in the switch it would come on - irrespective of the switched position!) All a bit of a disaster wiring wise– but the correct term to describe the switching remains incorrect polarity – as the switch is not in the phase conductor only. Note 1* This is why ISOLATION is much more preferable to switching off for maintenance – breaking both poles would eradicate the risk in this case, although the problem would still be in place.
Fuses & Circuit Breakers: Fundamental defects Loss of Supply Potential cause: 1.Overload (time to trip or blow will determine the likelihood)
An earth fault on one phase of a 3 phase supply will disconnect that phase – while the remaining two exert to rotate the apparatus. This is often identified by overheating, buzzing or humming coming from a motor, or the machine thrusting with uneven momentum when attempting to rotate. Newly Installed work – CB’s tripping once power is energised. The same test methods are used for new & existing circuits to locate a fault – but a ‘starting-point’ is the critical element for fast and effective rectification.
Testing to locate the position of a Fault.
If you are convinced that the Earth is touching the phase (or vice-versa), or the PH is touching the N prior to the load, then you would carry out an IR test at 500 Volts DC between the Ph & E or Ph & N. If a reading of 0.00Ω was seen, then the two cables being tested are in contact with each other. If the reading were less than the maximum for the instrument being used (ie a meter that would normally read >999MΩ was indicating 329MΩ) – and was dropping as the test were being carried out, part of the circuit would be seen as erroneous, and must be further investigated.
From the above, if a reading of 0.00Ω was seen, then the two cables being tested are in contact with each other at some point in that circuit. To locate the point the circuit must next be disconnected as near to its mid-point as possible. One side would read >999MΩ, and the other would continue to read 0.00Ω. The healthy side can now be disregarded and the half-test carried out again on the damaged side of the circuit. Murray Loop Test
where A & B are variable resistor readings, and L&X cable lengths.
Discrimination: Conventional Paradigms General Fig. 1
From Fig 1 above, if another five 500watt halogen fittings were added to the circuit controlled by the 13A fused spur, the fuse in the spur would (eventually) overload. However, if the phase in one of the fittings were to touch the earth, in this case the RCD would operate. Theoretically, if a Dead-Short occurred across the cable supplying the Fused spur the Main fuse would operate, although if the halogen lighting brought the load protected by the 32A ring to a figure in excess of its 32Amp rating the CB would disconnect (in due course), etc, etc... so discrimination describes the correct device operating at an essential time in the event of either the cable or the load being rendered unsafe. Industry Fig 2.
Figure 2 illustrates such a circuit, where a 16A BSEN60898 Type C circuit breaker is wired in line with an Isolator containing a 16Amp BS88 fuse. While these are effectively carrying out the same job, the fuse is part of an isolation device, which is in place for a different purpose to the Circuit breaker at the DB. However, each of the faults listed above would result in a different device operating. For example, a restriction to the movement of the motor, causing it to draw more load may well operate the Control fuse prior to any of the more sensitive devices, while a dead short across the coil to neutral would most lily cause the CB to trip before the 16A BS88 in the isolator (which is closer to the load). Intriguingly in this case the use of a 100mA RCD as a main switch could well give rise to nuisance tripping throughout the life-span of the installation, because the discriminatio0n of the device would be seen to be incorrect.
Conclusion: There are only a certain number of reasons why a circuit will have ceased to operate as it should. As an Electrician becomes more experienced & encounters more of these faults they come to recognise them very quickly, and then they just need to prove their conjecture by safely testing the circuit to reaffirm their initial assumptions. Rectification is often straightforward once the fault is identified... Download this Page in PDF Format
|